1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 120/192
ASUn Solar panel water pump mintenance
Label on alarm
visualization menu
ASUn (Domestic hot water pump maintenance)
Pump running hours > Hour counter setpoint
Hour reset in function menu
On the display the symbol is blinking
Only display warning messages
AtAS Domestic hot water pump overload alarm
Label on alarm
visualization menu
AtAS (domestic hot water pump overload)
Automatic reset if number of alarms per hour < AL75.
Manual reset if number of alarms per hour = AL75 (reset procedure in function
menu).
On the display the symbol is blinking
Domestic hot water pump OFF
AtC1 - AtC2 Condenser pump overload alarm
Label on alarm
visualization menu
AtC1 (overload pump alarm of condenser 1)
AtC2 (overload pump alarm of support condenser 2)
Active ID when it is configured as overload pump of condenser 1
Active ID when it is configured as overload pump of condenser 2.
With active digital input
Manual (reset procedure in function menu).
On the display the symbol is blinking
Condenser water pump and compressors OFF
AtE1 - AtE2 Evaporator pump overload alarm
Label on alarm
visualization menu
AtE1 (overload pump alarm of evaporator 1)
AtE2 (overload pump alarm of support evaporator 2)
Active ID when it is configured as overload pump of evaporator 1
Active ID when it is configured as overload pump of support evaporator 2.
With active digital input
Manual (reset procedure in function menu).
On the display the symbol is blinking
Evaporator water pump and compressors OFF
AtHS Domestic hot water heaters overload alarm
Label on alarm
visualization menu
AtHS (domestic hot water heaters overload)