EasyManua.ls Logo

Emerson Dixell iChill IC207D - Page 145

Emerson Dixell iChill IC207D
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 145/192
CF 2
Selection type rof unit
1= only chiller
2= only heat pump
3= chiller and heat pump
1
3
CF 3
Condensing unit
0= no
1= si
0
1
CF 4
Compressors number for circuit 1
1= 1
2= 2
3= 3
4= 4
1
4
CF 5
Compressors number for circuit 2
0= 0
1= 1
2= 2
3= 3
0
3
CF 6
Number of compressor parzialization
0= none
1= 1
2= 2
3= 3
0
3
CF 7
Pressure or temperature analogue input functioning
0 = Temperature / pressure NTC 4÷20 mA :
The condensing temperature is controlled with NTC probe while for the
evaporating pressures of the circuits 1 and 2 and the pressure probe
configured as auxiliary output 1 and 2 are controlled with 4÷20mA
transducers.
1 = Pressure control with 4÷20 mA:
To control the evaporating and condensing pressures it is necessary a
4÷20mA transducer.
2 = Temperature / pressure NTC 0÷5Vdc:
The condensing temperature is controlled with NTC probe while for the
evaporating pressures of the circuits 1 and 2 and the pressure probe
configured as auxiliary output 1 and 2 are controlled with 0÷5Vdc transducers.
3 = Pressure control with 0÷5Vdc:
To control the evaporating and condensing pressures it is necessary a
ratiometric 0÷5Vdc transducer.
0
3
CF 8
PB1 Configuration
If configured as digital input
0
o 1
29
c94
CF 9
PB2 Configuration
If configured as digital input
0
o 1
29
c94
CF 10
PB3 Configuration
If configured as digital input
0
o 1
36
c94
CF 11
PB4 Configuration
If configured as digital input
0
o 1
36
c94
CF 12
PB5 Configuration
If configured as digital input
0
o 1
29
c94
CF 13
PB6 Configuration
If configured as digital input
0
o 1
29
c94
CF 14
PB7 Configuration
If configured as digital input
0
o 1
29
c94
CF 15
PB8 Configuration
If configured as digital input
0
o 1
29
c94
CF 16
PB1 Offset
-12.0
-21
12.0
21
°C
°F
Dec
int
CF 17
PB2 Offset
-12.0
-21
12.0
21
°C
°F
Dec
int
CF 18
PB3 Offset
-12.0
-21
-5.0
-72
12.0
21
5.0
72
°C
°F
bar
psi
Dec
int
dec
int
CF 19
PB4 Offset
-12.0
-21
-5.0
-72
12.0
21
5.0
72
°C
°F
bar
psi
Dec
int
dec
int
CF 20
PB5 Offset
-12.0
-21
-5.0
-72
12.0
21
5.0
72
°C
°F
bar
psi
Dec
int
dec
int
CF 21
PB6 Offset
-12.0
-21
-5.0
-72
12.0
21
5.0
72
°C
°F
bar
psi
Dec
int
dec
int