1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 146/192
CF 22
PB7 Offset
-12.0
-21
-5.0
-72
12.0
21
5.0
72
°C
°F
bar
psi
Dec
int
dec
int
CF 23
PB8 Offset
-12.0
-21
-5.0
-72
12.0
21
5.0
72
°C
°F
bar
psi
Dec
int
dec
int
CF 24
Pressure value at 4mA or 0.5 Vdc of the PB3 transducer
-1.0
-14
50.0
725
Bar
psi
Dec
int
CF 25
Pressure value at 20mA or 5 Vdc of the PB3 transducer
-1.0
-14
50.0
725
Bar
psi
Dec
int
CF 26
Pressure value at 4mA or 0.5 Vdc of the PB4 transducer
-1.0
-14
50.0
725
Bar
psi
Dec
int
CF 27
Pressure value at 20mA or 5 Vdc of the PB4 transducer
-1.0
-14
50.0
725
Bar
psi
Dec
int
CF 28
Pressure value at 4mA or 0.5 Vdc of the PB5 transducer
-1.0
-14
50.0
725
Bar
psi
Dec
int
CF 29
Pressure value at 20mA or 5 Vdc of the PB5 transducer
-1.0
-14
50.0
725
Bar
psi
Dec
int
CF 30
Configuration of ID1
0
c94
CF 31
Configuration of ID2
0
c94
CF 32
Configuration of ID3
0
c94
CF 33
Configuration of ID4
0
c94
CF 34
Configuration of ID5
0
c94
CF 35
Configuration of ID6
0
c94
CF 36
Configuration of ID7
0
c94
CF 37
Configuration of ID8
0
c94
CF 38
Configuration of ID9
0
c94
CF 39
Not used
0
0
CF 40
Not used
0
0
CF 41
Configuration of RL1
0
c80
CF 42
Configuration of RL2
0
c80
CF 43
Configuration of RL3
0
c80
CF 44
Configuration of RL4
0
c80
CF 45
Configuration of RL5
0
c80
CF 46
Configuration of RL6
0
c80
CF 47
Configuration of RL7
0
c80
CF 48
Not used
0
0
CF 49
Analog output selection
0= 0..10V
1= 4..20mA
0
1
CF 50
Proportional output OUT 1
0= not configured
1= modulation evaporator water pump 0÷10V
2= Free cooling modulating output 0÷10V
3= not used
4= auxiliary output AUX1 0÷10V
5= auxiliary output AUX2 0÷10V
6= inverter compressor 1 0÷10V
7= inverter compressor 2 0÷10V
8= modulating condenser fan circuit 1 0÷10V
9= modulating condenser fan circuit 2 0÷10V
o1..c50 ON / OFF with the same meaning of reconfiguration
0
o 1
9
c54
CF 51
Not used
CF 52
Proportional output OUT 2
0= not configured
1= modulation evaporator water pump 0÷10V
2= Free cooling modulating output 0÷10V
3= not used
4= auxiliary output AUX1 0÷10V
5= auxiliary output AUX2 0÷10V
6= inverter compressor 1 0÷10V
7= inverter compressor 2 0÷10V
8= modulating condenser fan circuit 1 0÷10V
9= modulating condenser fan circuit 2 0÷10V
10= modulating condenser fan circuit 1 PWM
11= modulating condenser fan circuit 2 PWM
o1..c50 ON / OFF output with the same meaning of relè
0
o 1
11
c54