Proportional output OUT 3
0= not configured
1= modulation evaporator water pump 0÷10V
2= Free cooling modulating output 0÷10V
3= not used
4= auxiliary output AUX1 0÷10V
5= auxiliary output AUX2 0÷10V
6= inverter compressor 1 0÷10V
7= inverter compressor 2 0÷10V
8= modulating condenser fan circuit 1 0÷10V
9= modulating condenser fan circuit 2 0÷10V
10= modulating condenser fan circuit 1 PWM
11= modulating condenser fan circuit 2 PWM
o1..c50 ON / OFF output with the same meaning of relè
Remote keyboard 1 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
Remote Panel 2 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
Offset of the probe of the remote terminal 1
Offset of the probe of the remote terminal 2
Icon function
0= chiller / heat pump
1= chiller / heat pump
0= Chiller / Heat pump selection by keyboard
1= Chiller / Heat pump selection by digital input
2= Chiller / Heat pump selection by analogue input
Automatic change over setpoint for chiller/ heat pump selection (CF79 = 2)
Automatic change over differential (CF79 = 2)
°C or °F selection
0= °C / °BAR
1= °F / °psi
Power supply frequency
0= 50 Hz
1= 60 Hz
2= Vcc power supply
(ATTENTION
When CF83 = 2 the proportional outputs for fan control are not enabled)
Firmware Release (only reading)
Eeprom parameter map (only reading)
Maximum number of start up of the compressor in 15 minutes
0= Not enabled
Working mode of the compressor
0 = chiller and heat pump
1 = only chiller
2 = only heat pump
Buzzer presence (0=disabled, 1=enabled)
Chiller operation (1=only compressor; 2=only Free cooling; 3=compressors
and Free cooling)
Enable I/O expansion
0= not enabled
1= enabled
Enable expansion valve 1
0= not enabled
1= enabled
Enable expansion valve 2
0= not enabled
1= enabled