1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 147/192
CF 53
Proportional output OUT 3
0= not configured
1= modulation evaporator water pump 0÷10V
2= Free cooling modulating output 0÷10V
3= not used
4= auxiliary output AUX1 0÷10V
5= auxiliary output AUX2 0÷10V
6= inverter compressor 1 0÷10V
7= inverter compressor 2 0÷10V
8= modulating condenser fan circuit 1 0÷10V
9= modulating condenser fan circuit 2 0÷10V
10= modulating condenser fan circuit 1 PWM
11= modulating condenser fan circuit 2 PWM
o1..c50 ON / OFF output with the same meaning of re
0
o 1
11
c54
CF 54
Remote keyboard 1 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
0
2
CF 55
Remote Panel 2 configuration
0= Not enabled
1= Enabled model with ambient temperature sensor
2= Enabled model without ambient temperature sensor
0
2
CF 56
Offset of the probe of the remote terminal 1
-12.0
-21
12.0
21
°C
°F
Dec
int
CF 57
Offset of the probe of the remote terminal 2
-12.0
-21
12.0
21
°C
°F
Dec
int
CF 58
Icon function
0= chiller / heat pump
1= chiller / heat pump
0
1
CF 59
0= Chiller / Heat pump selection by keyboard
1= Chiller / Heat pump selection by digital input
2= Chiller / Heat pump selection by analogue input
0
2
CF 60
Automatic change over setpoint for chiller/ heat pump selection (CF79 = 2)
-50.0
-58
110.0
230
°C
°F
Dec
int
CF 61
Automatic change over differential (CF79 = 2)
0.1
0
25.0
45
°C
°F
Dec
int
CF 62
°C or °F selection
0= °C / °BAR
1= °F / °psi
0
1
CF 63
Power supply frequency
0= 50 Hz
1= 60 Hz
2= Vcc power supply
(ATTENTION
When CF83 = 2 the proportional outputs for fan control are not enabled)
0
2
CF 64
Serial address
1
247
CF 65
Firmware Release (only reading)
Only reading
CF 66
Eeprom parameter map (only reading)
Only reading
CF 67
Compressor 1 capacity
0
100%
CF 68
Compressor 2 capacity
0
100%
CF 69
Compressor 3 capacity
0
100%
CF 70
Compressor 4 capacity
0
100%
CF 71
Compressor 5 capacity
0
100%
CF 72
Compressor 6 capacity
0
100%
CF 73
Maximum number of start up of the compressor in 15 minutes
0= Not enabled
0
15
CF 74
Working mode of the compressor
0 = chiller and heat pump
1 = only chiller
2 = only heat pump
0
2
CF 75
Enable hybrid exchangers
0
1
CF 76
Buzzer presence (0=disabled, 1=enabled)
0
1
CF 77
Chiller operation (1=only compressor; 2=only Free cooling; 3=compressors
and Free cooling)
1
3
CF 78
Enable I/O expansion
0= not enabled
1= enabled
0
1
CF 79
Enable expansion valve 1
0= not enabled
1= enabled
0
1
CF 80
Enable expansion valve 2
0= not enabled
1= enabled
0
1