Enable condenser antifreeze heaters in OFF or STAND-BY
0= always off
1= enabled (ON or OFF depending on regulation request)
Condenser antifreeze heaters status in case of probe faulty
0 = OFF
1= ON
Pompa acqua condensatore per funzionamento antigelo
Enable condenser water pump in OFF or STAND-BY
Pompa/e acqua condensatore per antigelo in OFF o Stand-by
0= always off
1= enabled (ON or OFF depending on regulation request)
Condenser water pump probe selection for antifreeze operation
0= water pump not used per antifreeze
1= condenser common inlet probe
2= condenser common inlet probe, and condenser inlet circuit 1 probe, and
condenser inlet circuit 2 probe
3= condenser outlet circuit 1 probe and condenser outlet circuit 2 probe
4= condenser common outlet probe, and condenser outlet circuit 1 probe, and
condenser outlet circuit 2 probe
5= external temperature probe
Set point condenser water pump for antifreeze
Differential condenser water pump for antifreeze
Allarme antigelo condensatore
Condenser antifreeze alarm delay starting from unit switching on
Condenser antifreeze alarm delay in chiller
Condenser antifreeze alarm events per hour to generate manual reset alarm
in chiller
Condenser antifreeze alarm delay in heating
Condenser antifreeze alarm events per hour to generate manual reset alarm
in heat pump
Defrost configuration:
0= Not enabled
1= Start and stop for temperature / pressure
2= Start depends on probe selected by par. dF24 and stop for time duration
(dF05)
3= Start depends on probe selected by par. dF24 and stop for external
contact
4= Defrost only with condenser fan
5= Start from digital input and stop on probe selected by par. dF24
Temperature or pressure of the defrost start-up
Temperature or pressure of the defrost stop
Minimum defrost duration.
Maximum defrost duration.
Time delay between the defrost of two circuits
OFF compressor delay before the defrost
OFF compressor delay after the defrost
Defrost interval time of the same circuit
Temperature setpoint for combined defrost of the 1st circuit
Temperature setpoint for combined defrost end of the 1st circuit
Temperature setpoint for combined defrost of the 2nd circuit
Temperature setpoint for combined defrost end of the 2nd circuit
Activation of all the steps of the 1st circuit during the defrost.
0= Not enabled
1= Enabled
Activation of all the steps of the 2nd circuit during the defrost.
0= Not enabled
1= Enabled
Time delay between two compressor ON in defrost mode