1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 161/192
Fan control during defrost / dripping time
0= Not enabled
1= Only in defrost
2= For both functions defrost / dripping time
Pressure / temperature setpoint to force the ventilation ON during the defrost.
Minimum time delay before a forced defrost
Pressure / temperature setpoint for a forced defrost
Forced defrost differential
Defrost start-up with 2 circuits
0= Independent
1= If both have reached the necessary requirements
2= If one has reached the necessary requirements
End defrost for two circuits and common ventilation.
0= Independent
1= If both have reached the necessary end defrost requirements
2= If one has reached the necessary end defrost requirements
Start / stop defrost probe
0= start and stop with condenser temperatur / pressure probe
1= start with evaporator pressure probe / stop with condenser temperatur /
pressure probe
2= start with condenser temperatur / pressure probe / stop with evaporator
pressure probe
3= start and stop with evaporator pressure probe
Stop supply fan diuring defrost cycle
0= Not enabled
1= enable
Set point to enable defrost with condenser fan
Hybrid exchangers set point 1 in chiller
Hybrid exchangers set point 2 in chiller
Hybrid exchangers differential 1 in chiller
Hybrid exchangers differential 2 in chiller
Hybrid exchangers set point 1 in heat pump
Hybrid exchangers set point 2 in heat pump
Hybrid exchangers differential 1 in heat pump
Hybrid exchangers differential 2 in heat pump
Probe selection of the Hybrid exchangers
0= outside temperature
1= condenser temperature/pressure
Forced time Hybrid exchangers in chiller mode when the compressor is
switched on