1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 162/192
dF 37
Max. offset of the Defrost dinamic set point
-30.0
-54
-14.0
-203
30.0
54
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
dF 38
Outside temperature set point of the Defrost dinamic set point
-50.0
-58
110.0
230
°C
°F
Dec
int
dF 39
Outside temperature differential of the Defrost dinamic set point
-30.0
-54
30.0
54
°C
°F
Dec
int
Parameter
Description
min
max
M. u.
Resolution
rC 1
Domestic hot water regulation mode
0
2
rC 2
Recovery modes
0 = not enabled
1 = 2 indipendent circuit
2 = both the circuit in parallel
0
250
Sec
rC 3
Delay time delay with step forced off
0
250
Sec
rC 4
Delay time delay with step forced off after the recovery valve activation
0
250
Min
rC 5
Recovery minimum time
0
250
Min
rC 6
Minimum interval time between the end and the beginning of the next
recovery
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 7
Temperature setpoint to disable the recovery
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 8
Temperature differential to restore the recovery
0
250
Min
rC 9
Maximum time with recovery disabled (if temperature/pressure within rC6-
rC7)
0
1
rC 10
Set point heat recovery
rC11
rC12
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 11
Minimum value of the heat recovery set point
-50.0
-58
0.0
0
rC10
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 12
Maximum value of the heat recovery set point
rC10
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
rC 13
Differential heat recovery
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Parameter
Description
min
max
M. u.
Resolution
FS 1
Domestic hot water regulation mode
0= not enabled
1=valves in water circuit
2=valves in gas circuit
0
2
FS 2
Domestic hot water thermoregulation priority
0 = heating / cooling
1 = domestic hot water
2 = domestic hot water by digital input
0
2
FS 3
Domestic hot water thermoregulation set point
FS05
FS06
°C/°F
dec/int
FS 4
Domestic hot water thermoregulation band
0.1
0
25.0
45
°C
°F
Dec
int
FS 5
Minimum value of the domestic hot water set point
-50.0
-58
FS06
°C
°F
Dec
int
FS 6
Maximum value of the domestic hot water set point
FS05
110.0
230
°C
°F
Dec
int
FS 7
Full loads enabling to reach the domestic hot water set point
0
1
FS 8
Heaters enabling during the domestic hot water thermoregulation
0= not enabled
1= compressors + heaters
2= only heaters
3= only compressors
0
1
FS 9
Operation working time to activate the heaters during the domestic hot
water thermoregulation
0
250
Min
FS 10
Time delay to activate the domestic hot water valve
0
999
sec
int
FS 11
Reversing cycle delay during domestic hot water thermoregulation
0
999
sec
int
FS 12
Antilegionella function operating mode
0 = interval time
1= weekly
2= daily
0
2