1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 163/192
FS 13
Delay time between two Antilegionella cycles
0
250
Hr
0
FS 14
Antilegionella Set point
FS15
FS16
°C/°F
dec/int
FS 15
Minimum value of the Antilegionella set point
-50.0
-58
FS14
°C
°F
Dec
int
FS 16
Maximum value of the Antilegionella set point
FS14
110.0
230
°C
°F
Dec
int
FS 17
Hour selection for the Antilegionella activation
0
24.00
Hr
10 min
FS 18
Day selection for the Antilegionella activation
0
7
FS 19
Minimum operating working time of the Antilegionella cycle
1
250
min
FS 20
Temperature band for heaters deactivation during Antilegionella cycle
0.1
0
25.0
45
°C
°F
Dec
int
FS 21
Temperature differential to enable the freecooling function
0.1
0
25.0
45
°C
°F
Dec
int
FS 22
Temperature differential for the free cooling regulation
0.1
0
25.0
45
°C
°F
Dec
int
FS 23
Set point for solar panel activation
FS25
FS26
°C/°F
dec/int
FS 24
Differential value for solar panel deactivation
0.1
0
25.0
45
°C
°F
Dec
int
FS 25
Minimum value of the solar panel set point
-50.0
-58
FS23
°C
°F
Dec
int
FS 26
Maximum value of the solar panel set point
FS23
110.0
230
°C
°F
Dec
int
FS 27
Delay time to activate the domestic hot water valve starting from pump
activation
0
250
sec
FS 28
Delay time to deactivate the domestic hot water pump starting from valve
deactivation
0
250
sec
FS 29
Maximum operating working time of the Antilegionella cycle
0
250
min
FS 30
Domestic hot water: security set point
-50.0
-58
110.0
230
°C
°F
FS 31
Domestic hot water: security differential
0.1
0
25.0
45
°C
°F
FS 32
Domestic hot water: minimum interruption time
0
250
min
FS 33
Domestic hot water pump operation mode
0
1
FS 34
Free cooling water pump OFF time if chiller only Free cooling
0
250
min
FS 35
Free cooling water pump ON time if chiller only Free cooling
0
250
sec
FS 36
Free cooling maximum time
0
250
min
FS 37
Set point Free cooling
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
FS 38
Proportional band Free coling
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FS 39
Minimum value Free cooling analog output
0
100
%
FS 40
Maximum value Free cooling analog output
0
100
%
FS 41
T1 probe selection for Free cooling
0=disabled, 1=Pb1, 2=Pb2, etc.
0
22
FS 42
T2 probe selection for Free cooling
0=disabled, 1=Pb1, 2=Pb2, etc.
0
22
FS 43
Outside temperature set point to force the maximum speed of condenser
fan
-50.0
-58
110.0
230
°C
°F
FS 44
Outside temperature differential to force the maximum speed of condenser
fan
0.1
0
25.0
45
°C
°F
FS 45
Delay time of condenser fan regulation during Free cooling
0
250
min
FS 46
Antilegionella cycle opreration mode
0= compressors and heaters
1= compressors are first inserted and then heaters
2= only heaters
3= only compressors
0
3
FS 47
Evaporator water pump enabled is Domestic hot water
0= enabled
1= disabled
0
1
FS 48
Probe selection to force exit from Domestic hot water
0= disabled
1= probe Pb1
2= probe Pb2
...
0
22
FS 49
Start production Domestic hot water
0= when all compressors are requested
1= when at least one compressor is requested
0
1