1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 164/192
FS 50
Set point to force OFF the compressors during antilegionella cycle
-50.0
-58
110.0
230
°C
°F
FS 51
Compressors safety time in domestic hot water
0= safety time enabled
1= safety time disabled
0
1
FS 52
Set point to enable heaters for low domestic hot water temperature
-50.0
-58
110.0
230
°C
°F
FS 53
Proportional band to enable heaters for low domestic hot water temperature
0.1
0
25.0
45
°C
°F
FS 54
Probe selection for low domestic hot water temperature
0= disabled
1= Pb1
2= Pb2
...
0
22
FS 55
Solar panel opration mode for domestic hot water
0= disabled
1= integration to heat pump
2= substitution to heat pump
0
2
FS 56
Solar panel opration mode for heating
0= disabled
1= integration to heat pump
2= substitution to heat pump
0
2
FS 57
Probe selection to calculate Dt of solar panel in domestic hot water
0= disabled
1= Pb1
2= Pb2
0
22
FS 58
Probe selection to calculate Dt of solar panel in heating
0= disabled
1= Pb1
2= Pb2
0
22
FS 59
Dt to enable solar panel in domestic hot water
0.1
0
25.0
45
°C
°F
Dec
int
FS 60
Dt to enable solar panel in heating
0.1
0
25.0
45
°C
°F
Dec
int
FS 61
Maximum operation time of solar panel if set point not reached
0
250
min
FS 62
Probe selection to disable the Free cooling for low temperature
0
22
FS 63
Set point to disable the Free cooling for low temperature
-50.0
-58
110.0
230
°C
°F
FS 64
Differential to disable the Free cooling for low temperature
0.1
0
25.0
45
°C
°F
FS 65
Delay time to enable compressor in free cooling
0
250
min
FS 66
Dfferential to enable free cooling analog output
0.1
0
25.0
45
°C
°F
Parameter
Description
min
max
M. u.
Resolution
AL 1
Low pressure alarm delay from analog and digital input
0
250
Sec
AL 2
Low pressure alarm delay from digital input after compressor stop if the low
pressure switch is used for the pump down.
AL02= 0 low pressure alarm not enable with compressor OFF
AL02 0 low pressure alarm enable after AL02 time with compressor OFF
0
250
10 Sec
AL 3
Low pressure alarm setpoint from analogue input
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
AL 4
Low pressure alarm differential from analogue input
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
bar
psi
Dec
int
Dec
Int
AL 5
Maximum number of low pressure events from digital/analogue inputs:
Manual reset if AL05 = 0
Automatic reset if AL05 =16
From automatic to manual reset if AL05= 1..15
0
16
AL 6
Low temperature/pressure alarm during defrost
0= Not enabled
1= Enabled
0
1
AL 7
Low temperature/pressure alarm delay during defrost
0
250
Sec
AL 8
Low temperature/pressure alarm with unit in OFF or stand by:
0 = Not enabled
1= Alarm enabled
0
1
AL 9
High temperature/pressure alarm from analogue input
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int