1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 165/192
High temperature/pressure alarm differential from analogue input
Low oil pressure / level delay from digital input
Minimum time for low oil pressure / level from digital input activation in normal
working condition.
Maximum number of low oil pressure/level events:
Always manual reset if AL13= 0
Always automatic reset if AL13 =16
From automatic to manual reset if AL13 = 1..15
Configuration
0= Not enabled
1= Only for chiller
2= Only for heat pump
3= For both chiller and heat pump
“Flow switch / supply fan overload” alarm delay after pump/fun activation.
Flow switch time activation before blocking evaporator water pump
“Flow switch / supply fan overload” activation time to generate the alarm
“Flow switch / supply fan overload” de-activation time to reset the alarm
Compressor overload alarm delay after compressor start-up
Maximum number of compressor overload alarm events
Always manual reset if AL20 = 0
Always automatic reset if AL20 =16
From automatic to manual reset if AL20 =1..15
Maximum number of pump down alarm events per hour in stop condition.
After this number the alarm is logged, displayed and signalled with alarm
relay + buzzer.
Manual reset if AL21 = 0
Automatic reset if AL21 =16
From automatic to manual reset if AL21 =1..15
Maximum number of pump down alarm events per hour in start-up condition.
After this number the alarm is logged, displayed and signalled with alarm
relay + buzzer.
Always manual reset if AL22 = 0
Always automatic reset if AL22 =16
From automatic to manual reset if AL21 =1..15 and parameter AL23 config.
Select if the pump down alarm must change from automatic to manual reset:
0= Always automatic reset
1= Manual reset after AL21 alarm events
Minimum antifreeze setpoint in chiller (from –30 °C to AL24)
Maximum antifreeze setpoint in chiller (from AL24 to 70 °C)
Setpoint temperature for low anti-freeze alarm, low ambient temperature
(air/air), low temperature air outlet (air/air). From AL24 to AL25.
Differential of alarm reset in Chiller mode for anti-freeze, low ambient air
temperature or low outlet air temperature alarms.
Alarm delay for anti-freeze, low ambient air temperature or low outlet air
temperature. The temperature must be lower than AL26 for this time duration
before having the alarm event.
Maximum number of alarm events anti-freeze, low ambient air temperature or
low outlet air temperature before changing from automatic to manual alarm
reset:
Always manual reset if AL29 = 0
Always automatic reset if AL29 = 16
From automatic to manual if AL29 = 1. .15
Anti-freeze alarm configuration in chiller
0= to turn the compressors off when the anti-freeze control probe is lower
than AL26 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are not activated.
1= to turn the compressors off when the anti-freeze control probe is lower
than AL26 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are activated.
Setpoint of the minimum limit in heat pump (va da – 30 °C a AL32)
Setpoint of the maximum limit in heat pump (va da AL31 a 70 °C)
Anti-freeze alarm setpoint in heat pump
Setpoint temperature for low anti-freeze alarm, low ambient temperature
(air/air), low temperature air outlet (air/air). (from AL31 to AL32)
Alarm differential in heat pump. To reset the anti-freeze, low ambient
Temperature (air/air), low temperature air outlet (air/air) alarms.