Emerson Dixell iChill IC207D - DISABLE - ENABLE A CIRCUIT; ENABLE OR DISABLE A SINGLE COMPRESSOR

Emerson Dixell iChill IC207D
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 22/192
5. Push SET: the bottom display shows PAS and the top display a blinking 0.
6. Insert the password (see parameter AL46)
7. If the password is OK the label ArST blinks for 5 seconds then the display returns to normal condition
read-out (probes).
8. If the password is not correct the display shows PAS again. in any case is possible to scroll the list with
UP or DOWN
9. To exit push the M key one time or wait the timeout.
THE ALARM LIST CONTAINS 100 EVENTS IN A FIFO STRUCTURE. WHEN THE MEMORY IS FULL
ANY NEW ALARM WILL ERASE THE OLDEST.
9.4 PASSWORD RESET ALARM LOG
Default value is 4.
9.5 DISABLE ENABLE A CIRCUIT
CrEn FUNCTION.
Label involved with CrEn function: Cr1E = circuit 1, Cr2E = circuit 2
DISABLE A CIRCUIT
Enter the function Menu
1. Use UP or DOWN keys to select CrEn on the bottom display
2. Push SET key: the bottom display Cr1E, top display En.
3. Select the circuit 1 or 2 with UP or DOWN (Cr1E or Cr2E).
4. Push SET key for 3 seconds when one of the two Cr1E, Cr2E label are displayed. The top display shows
the En blinking label, use the UP or DOWN to change in diS (Disabled) or En (Enabled). Then push SET
key to confirm the new selection. The display shows next circuit status.
5. To exit the CrEn function push MENU key or wait the timeout.
9.6 READ-OUT OF A CIRCUIT NOT ENABLED
If one circuit is disabled the bottom display shows diS alternated with the label name of the measurement
selected.
Circuit 1 = diS the bottom display shows b1dS = circuit 1 disabled.
Circuit 2 = diS the bottom display shows b2dS = circuit 2 disabled.
9.7 ENABLE OR DISABLE A SINGLE COMPRESSOR
COEn FUNCTION
Label involved in COEn function: CO1E = Compressor 1 status… CO6E = Compressor 6 status
The COEn function uses only the compressors configured by the corresponding output parameters.
Enter the function Menu
1. Use the UP or DOWN keys to select COEn.
2. Push SET key: bottom display = CO1E, top display = En
3. Select the compressor with UP or DOWN: CO2E - CO3E - CO4E CO5E CO6E if available.
4. Push SET for 3 seconds when the label corresponds to the compressor to disable: CO1E - CO2E -
CO3E - CO4E CO5E CO6E. Top display shows the blinking En label, use the UP or DOWN key and
change to diS (Compressor disabled) or En (compressor enabled) then push SET to confirm, the display
shows next item.
5. To exit the COEn function push MENU key or wait the timeout.
9.8 READ-OUT OF THE COMPRESSOR STARTS-UP
For each compressor is possible to show the number of starts-up.
COSn FUNCTION.
Label involved in COSn function: C1S number of compressor 1 starts-up .. C6S number of compressor 6
starts-up
The labels are displayed only if the corresponding output is present and configured
The number of starts-up is displayed on the top display, the resolution is x 10 (eg 2 means 20 starts, 20
means 200 starts)
Enter the function Menu
1. Use the UP or DOWN keys to select COSn.