2. Push SET one time: the label of the first load C1S is showed on the top display, the bottom display
shows the number x10.
3. With UP or DOWN scroll the compressor list.
4. To exit the Hour function push MENU key or wait the timeout
9.9 RESET THE STARTS-UP NUMBER
Enter the function Menu
1. Within the Hour function select, with UP or DOWN, the interested label: CS1, CS2, CS3, CS4, CS5,
CS6.
2. Push the SET keys for 3 seconds: the top display shows the running hours blinking value, then it shows
0 to confirm the reset. The next load label is automatically loaded.
3. To exit the Hour function push MENU key or wait the timeout.
9.10 HOW TO VISUALIZE 4..20MA DYNAMIC SET POINT PROBE
Enter the function Menu
1. Use the UP or DOWN keys to select PbUs.
2. Push SET one time: the value of the 4..20mA probe of the dynamic set point is visualized.
9.11 READ-OUT OF THE RUNNING HOURS
This menu allows to shows all the time running hours of the compressors, supply fan and pumps.
Hour FUNCTION to show the controlled load consumption
Label involved in the Hour function:
CO1H Compressor 1 running hours .. CO6H Compressor 6 running hours.
EP1H Evaporator water pump or Supply fan running hours
EP2H Support evaporator water pump running hours
CP1H Condenser water pump running hours
CP2H Support condenser water pump running hours
SAPH Domestic hot water pump running hours
PAPH Solar panel water pump running hours
FCPH Free cooling water pump running hours
The labels are displayed only if the corresponding output is present and configured.
The running hours is displayed on the top display, the resolution is x 10 hours (eg 2 means 20 hours, 20
means 200hours)
Enter the function Menu
1. Use the UP or DOWN keys to select Hour
2. Push SET key: bottom display = above labels, top display = hours x10. The time is on.
3. Use the UP or DOWN keys to scroll the list.
To exit the Hour function push MENU key or wait the timeout
9.12 RESET THE RUNNING HOUR
Enter the function Menu
1. Within the Hour function select, with UP or DOWN, the interested label: CO1H, CO2H, CO3H, CO4H,
CO5H, CO6H, EP1H, EP2H, CP1H, CP2H, SAPH, PAPH or FCPH.
2. Push the SET keys for 3 seconds: the top display shows the running hours blinking value, then it shows
0 to confirm the reset. The next load label is automatically loaded.
To exit the Hour function push MENU key or wait the timeout
9.13 READ-OUT OF THE PROPORTIONAL OUTPUT PERCENTAGE OF THE
CONDENSER FAN CONTROL
The proportional outputs of the two circuits, that control the fan speed, can be showed in the menu function.
Cond FUNCTION.
Label involved in Cond function.
Cnd1 output value of the condenser fan of the circuit 1.
Cnd2 output value of the condenser fan of the circuit 2.