1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 9/192
12
combined defrost tempereature
13
domestic hot water temperature 1
14
domestic hot water temperature 2
15
solar panel temperature
16
Recovery temperature
17
condenser temperature
18
condenser pressure
19
evaporator pressure
20
compressor oil pressure
21
real time clock
3.5 FORCED READ - OUT OF THE TOP AND BOTTOM DISPLAY
The dP03 parameter allows to have a pre-defined visualization.
dP03=0
The visualization is defined by parameters dP01 and dP02
dP03 = 1
Top display:
Evaporator water inlet temperature, Ein label.
Bottom display:
Evaporator 1 water outlet temperature, label Out1 or evaporator 2 water outlet temperature, label Out2
dP03 = 2
Top display:
Condenser 1 water inlet temperature, label CIn1 or Condenser 2 water inlet temperature, label CIn2
Bottom display
Condenser 1 water outlet temperature, label COu1 or condenser 2 water outlet temperature, label COu2
dP03 = 3
Top display of the circuit 1:
Condenser temperature Cdt1 / pressure CdP1 or Condenser temperature Cdt2 / pressure CdP2
Bottom display of the circuit 1
Evaporator pressure probe LP1 or Evaporator pressure probe LP2
3.6 VI622 / TI620: REMOTE TERMINAL 1 VISUALIZATION
If dP04=0 the display has the same visualization of the Ichill.
If dP04=1 upper display visualizes the temperature measured by the probe mounted in the remote terminal
1 (remote terminal must have internal temperature sensor)
3.7 VI622 / TI620: REMOTE TERMINAL 2 VISUALIZATION
If dP05=0 the display has the same visualization of the Ichill.
If dP05=1 upper display visualizes the temperature measured by the probe mounted in the remote terminal 2
(remote terminal must have internal temperature sensor)