9
Installation and Maintenance Manual
E2K-401-0817 Rev. 1
August 2017
MCP and Electrical Hook Up
3. FULL FRAME – Reversing Contactor with the addition of electronic plugin modules.
Figure 6 Full MCP Frame
Close Pushbutton
Selector Switch
Torque Switches
Limit Switch Contacts
Rever
Contactor
Open Pushbutton
Pilot Lamps
Fuse
Terminal Strip
Transformer
Limit Switch Gear Box
Space Heater
EIM Modular Control Package (MCP) is available congured in thousands of possible
combinations of electrical and electronic parts. Refer to WIRING DIAGRAM and EIM JOB
SPEC SHEET provided by EIM with each actuator.
3.2 Electrical Hook Up
Step 1. Move valve to mid-position by handwheel. This will allow sufcient time to
stop actuator in case of improper hookup or reversed power phases.
Step 2. Identify a means of removing power from actuator during check out.
Step 3. Be sure no erroneous remote control signal can be received causing actuator
to energize.
Step 4. Energize Open control to check operation of contactor and push buttons.
Open controls must move valve in Open direction. If valve Closes, actuator
must be stopped and the power leads reversed to correct voltage phasing or
improper eld wiring.
CAUTION:
If voltage is improperly phased, Torque and Limit Switches are not in circuit to protect valve.
Step 5. Seal all eld conduit entries in accordance with National Electric Code
requirements
Section 3: MCP and Electrical Hook Up