11
Installation and Maintenance Manual
E2K-401-0817 Rev. 1
August 2017
Geared Rotary Limit Switch Setting Instructions
2. Disengage spring loaded spur gear — Push Disengage Shaft (2) in Fig. 8 down, then
rotate 90° so that shaft is captured in down position. This disengages limit switch
gears from the spring loaded gear pinion assembly.
Figure 8
(2)
3. Line up LSO indicator: If switch rotor does not line with arrows on instruction plate as
shown in g. 9, rotate screwdriver in same direction noted in Step 1 until switch just
rotates. If indicators line up as shown in g. 9a, rotate screwdriver in the opposite
direction until switch just rotates, then slowly reverse direction to match g. 9a.
Figure 9
Fig.
9a
Re-engage spring loaded spur gear by turning Disengage Shaft (2) in Figure 8.
Disengage Shaft (2) will rise.
Section 4: Geared Rotary Limit Switch Setting Instructions