Appendix 1 Parameters 99
EV2000 Series Universal Variable Speed Drive User Manual
Group 7: Terminal Function Parameters
Para. Name LCD Display Setting Range Unit
Factory
setting
Modif
F7.10
Bi-direction
open
collector
output
terminal Y1
Y1 FUNC
SELE
0:Running signal(RUN)
1:frequency arriving signal(FAR)
2:frequency detection threshold (FDT1)
3:frequency detection threshold (FDT2)
4:overload signal(OL)
5:low voltage signal(LU)
6:external fault signal(EXT)
7:frequency high limit(FHL)
8:frequency low limit(FLL)
9:zero-speed running
10:Completion of simple PLC operation
11:PLC cycle completion indication
12:preset counting value arriving
13:specified counting value arriving
14:reference length arriving indication
15:drive ready (RDY)
16:drive fault
17:extended functions of host
18:Upper and lower limits of traverse operating frequency
19: preset operating time out
1 0
×
F7.11
Bi-direction
open
collector
output
terminal Y2
Y2 FUNC
SELE
1 1
×
F7.12
Function
selection of
output relay
RELAY
OUTPUT
1 16
×
F7.13 FAR duration FAR RANGE 0.00~650.0Hz 0.01Hz 2.50Hz
○
F7.14 FDT1 level FDT1 LEVEL 0.00~650.0Hz 0.01Hz 50.00Hz
○
F7.15 FDT1 lag FDT1 LAG 0.00~650.0Hz 0.01Hz 1.00Hz
○
F7.16 FDT2 level FDT2 LEVEL 0.00~650.0Hz 0.01Hz 25.00Hz
○
F7.17 FDT2 lag FDT2 LAG 0.00~650.0Hz 0.01Hz 1.00Hz
○
F7.18
~
F7.25
Reserved RESERVED - - 0 *
F7.26
Functions of
terminal AO1
ANALOG
OUTPUT1
0: Output frequency before slip compensation (0~Max output frequency)
1:Output frequency after slip compensation (0~Max output frequency)
2:Preset frequency (0~Max output frequency)
3:Output current (0~2 times of drive’s rated current)
4:Output current (0~2 times of motor’s rated current)
5:Output torque (0~2 times of motor’s rated torque)
6:Output voltage (0~1.2 times of drive’s rated voltage)
7:Bus voltage (0~800V)
8:VCI (0~10V)
9:CCI (0~10V/0~20mA)
10:Output power (0~2 times of rated power)
11:Extended function of host 2(0~65535)
1 0
○
F7.27
Functions of
terminal AO2
ANALOG
OUTPUT2
1 3
○
F7.28
Functions of
terminal DO(no
output when
F7.07=44~46)
DIGITAL
OUPUT
1 0
○
F7.29
Analog output
range
ANALOG
OUTPUT
OFFSET
Unit’s place of LED: AO1 offset selection
0: 0~10V or 0~20Ma 1: 2~10V or 4~20mA
Ten’s place of LED: AO2 offset selection
0:0~10V or 0~20mA 1: 2~10V or 4~20mA
1 00
○
F7.30
AO1 output
gain
A01 CALIB
0.0~200.0% 0.1% 100.0%
○
F7.31
AO2 output
gain
A02 CALIB
0.0~200.0% 0.1% 100.0%
○
F7.32
Maximum
output
frequency of
DO
MAX
OUTPUT
PULSE
0.1~50.0 (up to 50k) 0.1 10.0k
○
F7.33
Preset counting
value reaches
reference value
SET COUNT
VALUE
F7.34~9999 1 0
○
F7.34
Specified
counting value
SPECIFIED
COUNT
0~F7.33 1 0
○