Electrical Connections—UPS
Liebert
®
eXM
30
3.4.2 Output Dry Contacts
The Auxiliary Terminal Block has three output dry contact relays (see Figure 16 and Table 6).
Figure 16 Output dry contacts and EPO wiring
Table 6 Output dry contact relays
Port Pin
Name Description
J24
1 MFP_O Rectifier back-feed normally open contact. Open when there is no back-feed.
3 MFP_S Rectifier back-feed common contact.
5 MFP_C Rectifier back-feed normally closed contact. Closed when there is no back-feed.
J23
2 INV_O Inverter state normally open contact. Open when the inverter is abnormal.
4 INV_S Inverter state common contact.
6 INV_C Inverter state normally open contact. Closed when the inverter is normal.
J23
1 BFP_O Bypass back-feed normally open contact. Open when there is no back-feed.
3 BFP_S Bypass back-feed common contact.
5 BFP_C Bypass back-feed normally closed contact. Closed when there is no back-feed.
J24
2 MAIN_O Rectifier input state normally open contact. Open when the rectifier is abnormal.
4 MAIN_S Rectifier input state common contact.
6 MAIN_C Rectifier input state normally closed contact. Closed when the rectifier is normal.
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded
for maximum runs between 80 and 200 feet (25-60m), respectively.
BFP_O
J23
J25
J24
BFP_S
BFP_C
INV_O
INV_S
INV_C
MAIN_O
MAIN_S
MAIN_C
MFP_O
MFP_S
MFP_C
RESV_O
RESV_S
RESV_C
RESV_O
RESV_S
RESV_C
1
3
5
1
3
5
1
3
5
24
6
24
6
24
6