Option Installation
Liebert
®
 eXM
™
40
5.4.2 Liebert IntelliSlot
™
 Relay Card Jumper Setup
The Liebert IntelliSlot Relay Card has five jumpers, P3 through P7, as shown in Figure 25. Each 
jumper connects two pins.
Figure 25 Jumper location and numbering
By default all five jumpers have shunts installed. The two pins are shunted together to provide the 
functions shown in Table 12, allowing relay commons to be tied together.
The jumpers should be removed if there is any external voltage source that may intentionally or 
inadvertently be connected to the relay.
Removing the shunt from any two pins breaks the connection between the relay commons so they are 
not tied together.
Table 12 Jumper connections
Jumper Relay
P6 On Battery
P5 UPS Fault
P4 Low Battery
P3 On Bypass
P7 Summary Alarm
NOTE
Refer to the Liebert IntelliSlot Relay Card manual, SL-23211 for additional details. the 
document is available at the Liebert Web site, www.liebert.com
Jumper 
P6
Jumper 
P5
Jumper 
P4
Jumper 
P3
Jumper 
P7
Front 
of 
Card