Option Installation
Liebert
®
eXM
40
5.4.2 Liebert IntelliSlot
Relay Card Jumper Setup
The Liebert IntelliSlot Relay Card has five jumpers, P3 through P7, as shown in Figure 25. Each
jumper connects two pins.
Figure 25 Jumper location and numbering
By default all five jumpers have shunts installed. The two pins are shunted together to provide the
functions shown in Table 12, allowing relay commons to be tied together.
The jumpers should be removed if there is any external voltage source that may intentionally or
inadvertently be connected to the relay.
Removing the shunt from any two pins breaks the connection between the relay commons so they are
not tied together.
Table 12 Jumper connections
Jumper Relay
P6 On Battery
P5 UPS Fault
P4 Low Battery
P3 On Bypass
P7 Summary Alarm
NOTE
Refer to the Liebert IntelliSlot Relay Card manual, SL-23211 for additional details. the
document is available at the Liebert Web site, www.liebert.com
Jumper
P6
Jumper
P5
Jumper
P4
Jumper
P3
Jumper
P7
Front
of
Card