8.0 SPECIFICATIONS AND TECHNICAL DATA
8.1 Conformity and Standards
The Liebert eXM has been designed to conform to the following standards:
The Liebert eXM has UL and c-UL approval.
8.2 UPS Environmental
The Liebert eXM is designed to operate under the following environmental conditions without
damage or degradation in electrical operating characteristics:
Safety UL 1778 4th Edition, CSA 22.2 107.3
Surge IEC 61000-4-5 Criteria B
Harmonics IEC 61000-3-4
Electrical Fast Transient IEC 61000-4-4, Criteria B
ESD IEC 61000-4-2, Criteria B
FCC Part 15, Class A
Radiated Immunity IEC 61000-4-3, Criteria A
Conducted Immunity IEC 61000-4-6, Criteria A
Low-Frequency Signals IEC 61000-2-2 Criteria A
Transportation ISTA Procedure 1H
ISO 9001
Misc OSHA, ASME, NEMA PE-1
Table 21 Environmental requirements
Item Requirements
Acoustical Noise, dBA, at 55 in. (1.4m) 59
Operating Altitude
3281 ft. (1000m) 1% maximum kW derate per 328 ft. (100m) rise
between 3281 and 9843 ft. (1000m and 3000m)
Relative Humidity 95%
Operating Temperature, °F (°C) 104 (40)
UPS Storage/Transport Temperature, °F (°C) -4 to 158 (-20 to 70)
Table 22 UPS mechanical characteristics
Rated Power, kVA
60 - 100
Dimensions, W x D x H, in (mm) 23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000)
Weight, lb (kg) 955 (433)
Color RAL 7021 (Black)
Protection Degree IEC (60529) IP20