Operation
57 Liebert
®
eXM
™
Paralleling Mode
This option is available only on 208V Input Parallel with the optional Liebert eXM Paralleling
Cabinet. It can parallel the following:
• two Liebert eXM’s
• 60-100kW frames in any module capacity
•redundant
• can allow up to 200kW of load capacity
A sharing inductor and optional Liebert eXM Paralleling Cabinet are required for parallel units.
Output Voltage Adjustment
This feature allows a Liebert Customer Engineer to adjust the Liebert eXM’s output voltage over a
range of -5% to +5% of nominal. The output voltage adjustment can be used to compensate for any
drop in line voltage that may occur when the UPS is a significant distance from the protected load. In
addition, it can be used to optimize the UPS output voltage for loads that operate more efficiently at a
voltage different from the nominal Liebert eXM output voltage.
Generator Mode
The Liebert eXM UPS can be set up for operation in Generator Mode by an Emerson Network Power
Liebert Services engineer. The setup requires connecting J26 Pin 2 to Pin 4.
7.2 UPS Startup
The Liebert eXM must be fully installed and commissioned before startup, and external power
isolators must be closed. Once those general conditions are met, the UPS may be started.
AVERTISSEMENT
Risque d'arc ou de décharge électrique pouvant entraîner des dommages matériels, des
blessures et même la mort.
L'entrée et la sortie du système ASC doivent être protégées par des dispositifs de protection
de surintensité externes. En mode d'entretien, les barres omnibus d'entrée et de sortie
demeurent sous tension et présentent un risque de décharge électrique.
NOTE
To parallel non-208 input voltages, an upstream transformer must drop the input voltage to
208V before the paralleling gear.
WARNING
Risk of electrical shock. Can cause equipment damage, personal injury and death.
The following procedure provides power to the critical load distribution system. Verify that
the critical load distribution is ready to accept power. Make sure that personnel and
equipment are ready for the critical load distribution system to be energized.
AVERTISSEMENT
Risque de décharge électrique pouvant entraîner des dommages matériels, des blessures et
même la mort.
La procédure suivante fournit de l'énergie au système de distribution de la charge critique.
Vérifiez que ce système est prêt à être alimenté. Assurez-vous que le personnel et les
équipements sont préparés pour la mise sous tension du système de distribution de la charge
critique.