Maintenance
Liebert
®
eXM
™
80
BCB open BCB open from dry contact signal.
Battery Float Charging Battery is float charging.
Battery Boost Charging Battery is boost charging.
Battery Discharging Battery is discharging.
Battery Period Testing Battery is period self-testing.
Batt. Capacity Testing Battery is capacity self-testing.
Batt. Maint. Testing Battery is maintenance self-testing.
Inverter in Setting Inverter is in parameter setting.
Rectifier in Setting Rectifier is in parameter setting.
Batt. Converter Fault
Battery converter output voltage beyond limits or battery fuse failed. Battery converter shuts
down. Battery backup not available.
Operation Invalid This record is registered following an incorrect operation.
Byp. Abnormal Shutdown Both bypass and inverter voltages unavailable. Load interruption.
Mains Neutral Lost AC Input mains reference neutral not detected.
Battery Room Alarm Environment in battery room needs attention.
Rec Flash Update Rectifier firmware is being updated.
Inv Flash Update Inverter firmware is being updated.
Monitor Flash Update Monitor firmware is being updated.
LBS abnormal LBS is abnormal.
Table 38 UPS status messages (continued)
Event Message Description / Suggested Action (if any)