6.5.1 Configure a basic event
Display
Not available
ProLink II ProLink > Configuration > Events
ProLink III Device Tools > Configuration > Events > Basic Events
Field Communicator
Not available
Overview
A basic event is used to provide notification of process changes. A basic event occurs (is
ON) if the real-time value of a user-specified process variable moves above (HI) or below
(LO) a user-defined setpoint. You can define up to two basic events. Event status can be
queried via digital communications, and a discrete output can be configured to report
event status.
Procedure
1.
Select the event that you want to configure.
2. Specify Event Type.
Options Description
HI
x > A
The event occurs when the value of the assigned process variable (x) is
greater than the setpoint (Setpoint A), endpoint not included.
LO
x < A
The event occurs when the value of the assigned process variable (x) is
less than the setpoint (Setpoint A), endpoint not included.
3. Assign a process variable to the event.
4.
Set a value for Setpoint A.
5. (Optional) Configure a discrete output to switch states in response to the event
status.
6.5.2 Configure an enhanced event
Display
Not available
ProLink II ProLink > Configuration > Discrete Events
ProLink III Device Tools > Configuration > Events > Enhanced Events
Field Communicator Configure > Alert Setup > Discrete Events
Integrate the meter with the control system
Configuration and Use Manual 121