Emerson MICRO MOTION 2700 - 6.6.3 Configure Modbus;RS-485 communications

Emerson MICRO MOTION 2700
374 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Typical discrete output circuitFigure 6-1:
A. 24 V (Nom)
B.
3.2 K
C. Out+
D. Out
6.4.3 Configure Discrete Output Fault Action
Display
Not available
ProLink II ProLink > Configuration > Frequency/Discrete Output > Discrete Output > DO Fault Action
ProLink III Device Tools > Configuration > Fault Processing
Field Communicator Configure > Manual Setup > Inputs/Outputs > Discrete Output > DO Fault Action
Overview
Discrete Output Fault Action controls the behavior of the discrete output if the transmitter
encounters an internal fault condition.
Note
For some faults only: If Last Measured Value Timeout is set to a non-zero value, the transmitter will not
implement the fault action until the timeout has elapsed.
CAUTION!
Do not use Discrete Output Fault Action as a fault indicator. If you do, you may not be able to
distinguish a fault condition from a normal operating condition. If you want to use the discrete
output as a fault indicator, see Fault indication with the discrete output.