Quick Panel Operator User Manual Section 5
GFK-2847AA Jan 2023
Mounting and Installation 70
5.7.3 Serial Port Details
IC755CxS06RDx
Adhere to the following guidelines:
A terminal block is supplied with the unit.
The mating terminal block supports stranded 30 to 14 AWG (0.05 to
2.00 mm2) wires.
At a minimum, the cable must be rated for 75°C (167°F), or more.
Secure the serial cable to the mating connector while noting signal
orientation and tighten the screw clamps.
The torque for the attaching screws is 0.3 Nm (2.66 in-lb.).
Serial Port COM1 Details
Interface: x1 RS-232
Connector: Euro Terminal (Tyco Electronics 284539-5)
Mating Connector: Tyco Electronics 284510-5
Pin #
Signal Name
Pin-Out
1
TXD
Figure 73: Serial Port COM1 Pin-Out IC755CxS06RDx
2
RXD
3
RTS
4
CTS
5
SGND