EasyManua.ls Logo

Emerson ROSEMOUNT 5300 - Flameproof

Emerson ROSEMOUNT 5300
324 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
B-20
Flameproof
Figure B-22. Approval Labels
IECEx HART
E7 Flameproof
Ex iad IIC T4 (T
amb
:-40° C to +70 °C).
IECEx NEM 06.0001X.
U
m
=250 VAC
Conditions of Certification
The intrinsically safe circuits do not withstand the 500V AC test as specified in
EN 50020 clause 6.4.12.
Probes covered with plastic and/or with plastic discs will have a
non-conducting area that exceeds the maximum permissible area for Group
IIC accoring to IEC 60079-01 clause 7.3: 20 cm
2
for Zone 1 and 4 cm
2
for
Zone 0. Therefore, when the probe is used in a potentially explosive
atmosphere, appropriate measures must be taken to prevent electrostatic
discharge.
Impact and friction hazards need then to be considered according to IEC
60079-0 clause 8.1.2 when the transmitter exposed to the exterior
atmosphere of the tank is made with light metal alloys and used in Zone 0.

Table of Contents

Other manuals for Emerson ROSEMOUNT 5300

Related product manuals