Reference Manual
00809-0100-4530, Rev BA
July 2009
5-25
Rosemount 5300 Series
Volume
8. Choose Volume Calculation Method
HART command: [2, 1, 5].
F
OUNDATION Fieldbus parameters:
Calculation method:
TRANSDUCER 1300>VOL_VOLUME_CALC_METHOD
Tank Diameter:
TRANSDUCER 1300>VOL_IDEAL_DIAMETER
Tank Length:
TRANSDUCER 1300>VOL_IDEAL_LENGTH
Volume Offset:
TRANSDUCER 1300>VOL_VOLUME_OFFSET
To use volume calculation, choose a pre-defined calculation method based on
the tank shape that best corresponds to the actual tank. See “Volume
Configuration” on page 5-7.
Use the Strapping Table option if the actual tank does not match any of the
available options for pre-defined tanks, or if higher calculation accuracy is
desired.
Choose None if volume calculation is not desired at all.
The following standard tank shapes are available:
Vertical Cylinder
Horizontal Cylinder
Vertical Bullet
Horizontal Bullet
Sphere
•None
The following parameters must be entered for a standard tank shape:
Tank diameter
Tank height/length (not for spherical tanks)
Volume Offset: use this parameter if you do not want zero volume and
zero level to match (for example if you want to include a volume below
the zero level)