Situation #1 diagramFigure 7-8:
Solution to situation #1
Table 7-23 lists the appropriate configuration settings, and Figure 7-9 illustrates the correct
function block configuration.
Analog input function diagram for a pressure transmitter used in level
measurement (situation #1)
Table 7-23:
Parameter Configured values
L_TYPE Indirect
XD_SCALE 0 to 7 psi
OUT_SCALE 0 to 16 ft
Foundation Fieldbus
144 OCX 8800