Unidrive SP Regen Installation Guide 113
Issue Number: 2 www.controltechniques.com
Setting this parameter to 0 will disable the drive. It must be at 1 for the drive to run.
When this parameter is set up correctly for the local currency, Pr 6.26 will give an instantaneous read out of running cost.
If this parameter is one the energy meter (Pr 6.24 and Pr 6.25) is reset and held at zero.
To enable the feature that indicates to the user when a filter change is due Pr 6.18 should be set to the time between filter changes. When the drive is
running, Pr 6.27 is reduced each time the runtime timer hour increments (Pr 6.23) until Pr 6.27 reaches 0, at which point Pr 6.19 is set to 1 to inform
the user that a filter change is required. When the user has changed the filter, resetting Pr 6.19 to 0 will indicate to the drive that the change has been
done and Pr 6.27 will be reloaded with the value of Pr 6.18. Pr 6.27 can be updated with the value of Pr 6.18 at any time by setting and clearing this
parameter manually.
6.15 Drive enable
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1111
Default Regen 1
Update rate 4ms
6.16 Electricity cost per kWh
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1 111
Range Regen 0.0 to 600.0 currency units per kWh
Default Regen 0.0
Update rate Background
6.17 Reset energy meter
Drive mode Regen
Coding
BitSPFIDETEVMDPNDRANCNVPTUSRWBUPS
111
Default Regen 0
Update rate Background
6.18 Time between filter changes
Drive mode
Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1111
Range
Regen 0 to 30,000 hrs
Default
Regen 0
Update rate
Background
6.19 Filter change required / change done
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
111
Default Regen 0
Update rate Background
6.20 Powered-up time: years.days
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
311111
Range Regen 0 to 9.364 Years.Days
Update rate Background