Table 10-7 Losses @ 40°C (104°F) ambient with IP54 insert and standard fan fitted
Model
Drive losses (W) taking into consideration any current derating for the given conditions
Normal Duty Heavy Duty
Nominal
rating
3kHz 4kHz 6kHz 8kHz 12kHz 16kHz
Nominal
rating
3kHz 4kHz 6kHz 8kHz 12kHz 16kHz
kW hp kW hp
SP1201 1.1 1.5 33 35 38 42 49 56 0.75 1.0 27 29 32 35 41 47
SP1202 1.5 2.0 45 47 51 56 64 73 1.1 1.5 38 40 43 47 55 62
SP1203 2.2 3.0 67 70 76 78 1.5 2.0 51 53 58 62 71 78
SP1204 3.0 3.0 78 2.2 3.0 75 78
SP2201 4.0 5.0 155 161 173 186 210 235 3.0 3.0 133 139 150 160 182 203
SP2202 5.5 7.5 210 218 234 237 4.0 5.0 170 176 190 203 229 237
SP2203 7.5 10 237 5.5 7.5 237
SP1401 1.1 1.5 26 29 37 45 61 76 0.75 1.0 20 24 30 37 51 64
SP1402 1.5 2.0 34 38 48 57 76 78 1.1 2.0 27 31 39 48 64 78
SP1403 2.2 3.0 44 50 61 72 78 1.5 3.0 37 42 52 62 78
SP1404 3.0 5.0 62 69 78 2.2 3.0 52 58 70 78
SP1405 4.0 5.0 78 3.0 5.0 72 78
SP1406 5.5 7.5 78 4.0 5.0 78
SP2401 7.5 10 186 202 234 237 5.5 10 164 178 206 229 226
SP2402 11 15 237 7.5 10 201 218 230 224 223
SP2403 15 20 237 11 20 237