EasyManua.ls Logo

Emerson Unidrive M101 - Pr 05.027 Enable Slip Compensation

Emerson Unidrive M101
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running the
motor
Optimization NV Media Card
Advanced
parameters
Diagnostics UL Listing
Unidrive M100 / M101 Control User Guide 37
Issue Number: 1
Pr 00.041 {05.014} Control Mode (cont)
For mode 2 and 5, at low frequencies (from 0 Hz to ½ x Pr 00.039) a voltage boost is applied as defined by Pr 00.042 as shown below:
Pr 05.027 Enable Slip Compensation
When a motor, being controlled in open loop mode, has load applied a characteristic of the motor is that the output speed droops in proportion to the
load applied as shown:
In order to prevent the speed droop shown above slip compensation should be enabled. To enable slip compensation Pr 05.027 must be set to a
100 % (this is the default setting), and the motor rated speed must be entered in Pr 00.007 (Pr 05.008).
The motor rated speed parameter should be set to the synchronous speed of the motor minus the slip speed. This is normally displayed on the
motor nameplate, i.e. for a typical 18.5 kW, 50 Hz, 4 pole motor, the motor rated speed would be approximately 1465 rpm. The synchronous speed
for a 50 Hz, 4 pole motor is 1500 rpm, so therefore the slip speed would be 35 rpm. If the synchronous speed is entered in Pr 00.007, slip
compensation will be disabled. If too small a value is entered in Pr 00.007, the motor will run faster than the demanded frequency. The synchronous
speeds for 50 Hz motors with different numbers of poles are as follows:
2 pole = 3000 rpm, 4 pole = 1500 rpm, 6pole =1000 rpm, 8 pole = 750 rpm
Output
voltage
Pr / 2
00.008
Pr
00.008
Pr / 2
00.039
Pr
00.039
Output
frequency
Output voltage characteristic
(Fd)
Voltage boost
Pr
00.042
Pr 00.008
Pr
00.042
Pr 00.039
Pr + [(freq/Pr ) x (Pr - Pr )]00.042 00.039 00.008 00.039
2
Output
Voltage
Voltage
Boost
Output
Frequency
Shaft speed
Demanded speed
Load

Table of Contents

Other manuals for Emerson Unidrive M101

Related product manuals