Observing Time of Configurable Failure Inputs
P34
P34.0 - For Configurable Failure Input-1
P34.1 - For Configurable Failure Input-2
P34.2 - For Configurable Failure Input-3
0 0
0
0
0 - Observation Continuously
1 - Observation While Engine Running
0 - Observation Continuously
1 - Observation While Engine Running
0 - Observation Continuously
1 - Observation While Engine Running
0
0
1
1
1
Definition of Parameter
Operator Password
Technician Password
0 9990
0 9990
0
0
No
P37
P38
Min
Default
UnitMax
Configurable Failure Input-3
0 3
0 - Only horn temporary
1 - Only horn permanent
2 - Engine stop
3 - Contactor releaser
0
P33
Configurable Output-1
P35
0 - Alarm out
1 - Engine running
2 - Load permit
0 13 0
3 - Preheat
4 - Over speed
5 - High temperature
7 - Maintenance due
8 - Failed to start
9 - Over / under speed
10 - Voltage failure
6 - Low oil pressure
11 - Charging failure
12 - Low battery value
13 - Weak battery
Configurable Output-2
P36
0 13 0
0 - Alarm out
1 - Engine running
2 - Load permit
3 - Preheat
4 - Over speed
5 - High temperature
7 - Maintenance due
8 - Failed to start
9 - Over / under speed
10 - Voltage failure
6 - Low oil pressure
11 - Charging failure
12 - Low battery value
13 - Weak battery