The remote Emergency Stop button has been pressed and has shut down the engine. Press
Reset to remove the indication and restore unit operation.
9.1.8 Emergency Stop Message LED
9.1.9 Low Battery Voltage Message (bAT1)
This message appears if during engine cranking, the battery voltage drops below the value
specified by the Battery Voltage Weak Limit (P19) for longer than the period specified by the
Battery Voltage Weak Control Time (P20). The message is reset by Reset Button.
9.1.10 Weak Battery Alarm Message (bAT2)
The interval (hours run) between routine maintenance, set by Periodic Maintenance Hour Set
Value (P06), has expired. On completion of the required engine maintenance, reset the
maintenance timer using Periodic Maintenance Hour Reset (P07).
9.1.11 Routine Maintenance Due (SErV)
Isolate the equipment from the electricity supply during mechanical and
electrical maintenance. When this is not possible, the equipment must be in
the “OFF” position.
c
Symptom
Check all the wiring of the unit.
Check the Z supply. (measure voltage between pins 7 and 8)
Check the Z fuse.
Check engine oil level and pressure.
Check oil pressure switch and wiring.
Check engine temperature and cooling systems.
Check switch and wiring.
Check fuel solenoid and wiring, fuel and battery.
Reset the EAOM-6 and restart the engine.
Check solenoid transistor output activated,
(Fuel Solenoid if selected)
Unit is inoperative.
Possible Remedy
Low oil pressure fault
after engine has started
Failed to start fault.
Engine failed to start
after Number of Starting
Attempts (P23)
High engine
temperature fault after
engine has started
Check the signals that the EAOM-6 is using to determine if the
engine has started. Refer to the engine manual.
Check wiring to starter solenoid.
Check battery supply.
Check battery supply is present on the Start output (Pin3) of the
EAOM-6.
Starter motor
Inoperative.
37
When the battery voltage falls below the value specified by the Battery Voltage Lower Limit (P04).
The EAOM-6 measures battery voltage at the EAOM-6 terminals. This failure is indicated with an
error messages in EAOM-6. When this failure occurs in EAOM-6, the led with exclamation mark
starts to flash and user can see the error messages with the Scroll button .