Deltabar FMD72 Commissioning
Endress+Hauser 35
• The values entered for "Empty Calib./Full Calib.", "Empty Pressure/Empty Pressure"
and "Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a
warning message displayed, if the values are too close together. Further limit values are
not checked, i.e. the values entered must be appropriate for the sensor module and the
measuring task for the device to be able to measure correctly.
• Due to the orientation of the device, there may be pressure shifts in the measured value,
i.e. when the container is empty or partly filled, the measured value is not zero. For
information on how to perform position adjustment, see (® ä 32).
Description
1 Select the "Level" measuring mode via
the "Measuring mode (005)" parameter.
Menu path: Setup ® Measuring Mode
0 L
1000 L
450 mbar
50 mbar
1
2
3
r = 1
g
cm
A0017661
1 See table, steps 6 and 7.
2 See table, steps 8 and 9.
2 Select a pressure engineering unit via the
"Press Eng. Unit (125)" parameter, here
"mbar" for example.
Menu path: Setup ® Press Eng. Unit
3 Select the "In pressure" level mode via
the "Level Selection (024)" parameter.
Menu path: Setup ® Extended Setup
® Level ® Level Selection.
4 Select a volume unit via the "Unit before
lin. (025)" parameter, here "l" (liters) for
example.
Menu path: Setup ® Extended Setup
® Level® Unit before lin.