Deltabar S FOUNDATION Fieldbus Commissioning
Endress+Hauser 29
6.4.3 Quick Setup menu for the Flow measuring mode
P01-xxxxxxxx-19-xx-xx-xx-166
Fig. 10: Quick Setup menu for the Flow measuring mode
1) 1)2) 2)
1)
1) On-site display only
2) FieldCare only
PROFILE VIEW
MAX FLOW
MAX. PRESS. FLOW
POS. ZERO ADJUST
DAMPING VALUE
MEASURED VALUE
QUICK SETUP
GROUPSELECTION
MEASURING MODE MEASURING MODELANGUAGE
FlowPressure Level
QUICK SETUP OPERATING MENU
Onsite operation FieldCare
Measured value display
Switch from the measured value display to GROUP
SELECTION with F.
Measured value display
Select QUICK SETUP menu.
GROUP SELECTION
Select MEASURING MODE.
Measuring Mode
Select the Primary Value Type parameter.
MEASURING MODE
Select "Flow" option.
GROUP SELECTION
Select QUICK SETUP menu.
Primary Value Type
Select "Flow" option.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the
measured value. You correct the MEASURED VALUE via the
POS. ZERO ADJUST parameter with the "Confirm" option,
i. e. you assign the value 0.0 to the pressure present.
POS. ZERO ADJUST
Due to orientation of the device, there may be a shift in the
measured value. You correct the MEASURED VALUE via the
POS. ZERO ADJUST parameter with the "Confirm" option,
i. e. you assign the value 0.0 to the pressure present.
MAX. FLOW
Enter maximum flow of primary device.
(See also layout sheet of primary device).
MAX. FLOW
Enter maximum flow of primary device.
(See also layout sheet of primary device).
MAX. PRESS FLOW
Enter maximum pressure of primary device.
(See also layout sheet of primary device).
MAX. PRESS FLOW
Enter maximum pressure of primary device.
(See also layout sheet of primary device).