Deltabar S FOUNDATION Fieldbus Commissioning
Endress+Hauser 43
At a pressure of 350 mbar, the value 70 is output to a downstream block or to the PCS as the
OUT value.
P01-xMx7xxxx-05-xx-xx-xx-008
!
Note!
If you have selected the "Direct" mode for the L_TYPE parameter, you cannot change the
values and units for XD_SCALE and OUT_SCALE.
The L_TYPE, XD_SCALE and OUT_SCALE parameters can only be changed in the OOS block
mode.
Make sure that the output scaling of the Pressure Transducer Block SCALE_OUT matches the
input scaling of the Analog Input Block XD_SCALE.
0
1
0.7
0.7
1
0
700 100
L_TYPE: Indirect
Analog Input Block
XD_SCALE
OUT_SCALE
0
EU_0
500
EU_100
EU_0 EU_100
UNITS_INDEX:
mbar
UNITS_
INDEX:
%
OUT Value = 70
PRIMARY_VALUE
= 350 mbar
Output Pressure
Transducer Block