EasyManua.ls Logo

Endress+Hauser Deltapilot M FMB51 - Onsite Operation

Endress+Hauser Deltapilot M FMB51
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Deltapilot M FMB50/51/52/53
Endress+Hauser 49
Operating keys and elements located on the electronic insert
Onsite operation
P01-Mxxxxxxx-19-xx-xx-xx-001
HART electronic insert
1 DIP switch for locking/unlocking parameters
relevant to the measured value
2 DIP switch for switching damping on/off
3 DIP switch for alarm current SW / Alarm Min
(3.6 mA)
4 DIP switch only for Deltabar M
5 Slot for optional local display
6 Green LED to indicate successful operation
7 Operating keys for lower range value (zero)
and upper range value (span)
P01-Mxxxxxxx-19-xx-xx-xx-013
PROFIBUS PA electronic insert
1 DIP switch for locking/unlocking parameters
relevant to the measured value
2 DIP switch for switching damping on/off
3/4/5 Not used
6 DIP-switch for hardware address
7 DIP-switch for bus address SW / HW
8 Slot for optional local display
9 Operating key for position zero adjustment or
reset (Zero)
10 Green LED to indicate successful operation
P01-Mxxxxxxx-19-xx-xx-xx-014
FOUNDATION Fieldbus electronic insert
1 DIP switch for locking/unlocking parameters
relevant to the measured value
2 DIP switch for switching damping on/off
3 DIP-switch for simulation mode
4/5 Not used
6 Slot for optional local display
7 Green LED to indicate successful operation
8 Operating key for position zero adjustment or
reset (Zero)
on
off
SW / P2=High
SW / Alarm min
SW / Ö
damping
1
2
345
on
off
Display
Zero
Span
SW / P2=High
delta p only
SW / Alarm min
SW / Ö
damping
on
off
SW / P2=High
damping
1
2
345
➃➄
on:P2=
delta p
only
High off:SW
1
2
3
4
5
off:SW
on:
Ö
on
off
damp
not used
Address
SW
HW
Zero
on
off
Display
9
10
SW / Ö
on
off
SW / P2=High
Simulation
SW / Ö
damping
1
2
345
➃➄
on
off
Display
Zero
simulation
TM
F
OUNDATION
SW / P2=High
SW / Ö
damping
delta p only
Function Operation with operating keys and operating elements on the electronic insert
Analog electronics HART PROFIBUS PA FOUNDATION Fieldbus
Position adjustment (zero point correction) X X X X
Setting lower range value and upper range value -
reference pressure present at the device
X X -- --
Device reset XXX X
Locking and unlocking parameters relevant to the
measured value
-- X X X
Value acceptance indicated by the green LED X X X X
Switching damping on and off X X X X
Function Operation via display
Analog electronics HART PROFIBUS PA FOUNDATION Fieldbus
Position adjustment (zero point correction) -- X X X
Setting lower range value and upper range value -
reference pressure present at the device
-- X X X
Device reset -- X X X
Locking and unlocking parameters relevant to the
measured value
-- X X X
Value acceptance indicated by the green LED -- -- -- --
Switching damping on and off -- X X X

Table of Contents

Other manuals for Endress+Hauser Deltapilot M FMB51

Related product manuals