Commissioning Micropilot S FMR533 4 to 20 mA HART
48 Endress+Hauser
Function "check distance" (051)
This function triggers the mapping of interference echoes. To do so, the measured distance must be
compared with the actual distance to the product surface. The following options are available for
selection:
Selection:
•distance = ok
dist. too small
dist. too big
dist. unknown
manual
L00_FMR2xxxxx-14-00-06-en-010
distance = ok
mapping is carried out up to the currently measured echo
The range to be suppressed is suggested in the "range of mapping." (052) function
!
Note!
Anyway, it is wise to carry out a mapping even in this case.
dist. too small
At the moment, an interference is being evaluated
Therefore, a mapping is carried out including the presently measured echoes
The range to be suppressed is suggested in the "range of mapping." (052) function
dist. too big
This error cannot be remedied by interference echo mapping
Check the application parameters (002), (003), (004) and "empty calibr." (005)
dist. unknown
If the actual distance is not known, no mapping can be carried out.
manual
A mapping is also possible by manual entry of the range to be suppressed. This entry is made in the
"range of mapping." (052) function.
"
Caution!
The range of mapping must end 0.5 m (20") before the echo of the actual level. For an empty tank,
do not enter E, but E – 0.5 m (20"). If a mapping already exists, it is overwriten up to the distance
specified in "range of mapping" (052). Beyond this value the existing mapping remains
unchanged.