Commissioning (block-based operation) Levelflex FMP53 FOUNDATION Fieldbus
52 Endress+Hauser
11.7.3 Configurable area
An event category can be individually defined for the following parameters - irrespective of
the group of events they belong to by default.
F941: Echo lost
S942: In safety distance
Prior to changing the event category, the event must be allocated to one of the bits 1 to 15.
This is performed by the parameters FF912 ConfigArea_1 to FF912ConfigArea_15 in the
DIAGNOSTIC (TRDDIAG) block. Thereafter, the selected bit can be switched from 0 to 1 in
the desired allocation parameter.
Example
To change the category of error 942 "In safety distance" from Out of specification (S)
(default), to Function check (C), proceed as follows.
1.
Use the FieldCare navigation window to navigate to the the following screen: Expert →
Communication → Field diagnostics → Alarm detection enable.
2.
By default all Configurable Area Bits are set to not used.