Levelflex FMP53 FOUNDATION Fieldbus Commissioning (block-based operation)
Endress+Hauser 53
3.
Select one of these bits (in the example: Configurable Area Bit 1) and select In safety
distance from the associated drop-down menu. Confirm the selection by pressing the
Enter key.
4.
Got to the Offspec Map column and activate the checkbox of the respective bit (in the
example: Configurable Area Bit 1). Confirm the selection by pressing the Enter key.
A change of the error category of In safety distance does not affect an error which is
already present. The new category is only assigned if a new error of this type occurs after
the change.
11.7.4 Transmission of the event meassages to the bus
Event priority
Event messages are only transmitted to the bus if their priority is between 2 and 15. Events of
priority 1 are indicated on the display but not transmitted to the bus. Events of priority 0 are
ignored. By default, the priority is 0 for all events. The priority can be adjusted individually for
each allocation parameter. This is done by the following four priority parameters: