Levelflex FMP51, FMP52, FMP54
12 Endress+Hauser
Input
Measured variable
The measured variable is the distance between the reference point and the product surface.
Subject to the empty distance entered "E" the level is calculated.
Alternatively, the level can be converted into other variables (volume, mass) by means of
linearization (32 points).
Measuring range
The following table describes the media groups and the possible measuring range as a function of
the media group.
Levelflex FMP51, FMP54
Media group DC (ε
r
) Typical liquids
Measuring range
1)
bare metallic
rod probes
bare metallic
rope probes
coax probes
1 1.4...1.6 condensed gases, e.g. N
2
, CO
2
on request 6 m (20 ft)
2 1.6...1.9 liquefied gas, e.g. propane
solvent
Freon
palm oil
one-piece: 4 m (13 ft)
divisible: 10 m (33 ft)
15 to 22 m (49 to 72 ft) 6 m (20 ft)
3 1.9...2.5 mineral oils, fuels one-piece: 4 m (13 ft)
divisible: 10 m (33 ft)
22 to 32 m (72 to 105 ft) 6 m (20 ft)
4 2.5...4 benzene, styrene, toluene
furan
naphthalene
one-piece: 4 m (13 ft)
divisible: 10 m (33 ft)
32 to 42 m
(105 to 138 ft)
6 m (20 ft)
5 4...7 chlorobenzene, chloroform
cellulose spray
isocyanate, aniline
one-piece: 4 m (13 ft)
divisible: 10 m (33 ft)
42 to 45 m
(138 to 148 ft)
6 m (20 ft)
6 > 7 aqueous solutions
alcohols
ammonia
one-piece: 4 m (13 ft)
divisible: 10 m (33 ft)
45 m (148 ft) 6 m (20 ft)
1) The measuring range for interface measurement is limited to 10 m (33 ft).