Levelflex FMP51, FMP52, FMP54
Endress+Hauser 17
Protocol-specific data HART
Manufacturer ID 17 (0x11)
Device type ID 0x34
HART specification 6.0
Device description files (DTM,
DD)
Information and files at:
• www.endress.com
• www.hartcomm.org
HART load Min. 250 Ω
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Interface
1)
• Interface distance
1)
• Upper interface thickness
1)
• Electronic temperature
• Relative echo amplitude
• Relative interface amplitude
1)
Measured values for SV, TV, FV (second, third and fourth variable)
• Level linearized
• Distance
• Interface linearized
1)
• Interface distance
1)
• Upper interface thickness
1)
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Absolute interface amplitude
1)
• Relative interface amplitude
1)
• Calculated DC
Supported functions • Burst mode
• Additional transmitter status
1) only if an interface measurement is active
Wireless HART data
Minimum start-up voltage 11.4 V
Start-up current 3.6 mA
Start-up time 15 s
Minimum operating
voltage
11.4 V
Multidrop current 3.6 mA
Set-up time 1 s