EasyManua.ls Logo

Endress+Hauser Levelflex FMP54 - Mounting; Mounting Requirements

Endress+Hauser Levelflex FMP54
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex FMP51, FMP52, FMP54
22 Endress+Hauser
Energieversorgung
Terminal assignment 2-wire: 4-20mA HART
+
4...20 mA
4...20 mA
5
5
4
4
1
1
2
2
8
9
3
3
+
+
1
+
2
4...20mA
HART
10 mm
Spare part
71108xxx
2- wire level
4-20 mA 4-20 mA
HART
[21]
open
-
1
+
2
4-20mA
1-channel overvoltage protection
-
71128617
[16]
A
+
7
B
6
!
!
A0011294
 4 Terminal assignment 2-wire; 4-20mA HART
A Without integrated overvoltage protection
B With integrated overvoltage protection
1 Active barrier with power supply (e.g. RN221N): Observe terminal voltage
2 HART communication resistor (≥250 Ω): Observe maximum load
3 Connection for Commubox FXA195 or FieldXpert SFX350/SFX370 (via VIATOR Bluetooth modem)
4 Analog display device: Observe maximum load
5 Cable screen; observe cable specification
6 4-20mA HART (passive): Terminals 1 and 2
7 Overvoltage protection module
8 Terminal for potential equalization line
9 Cable entry

Table of Contents

Other manuals for Endress+Hauser Levelflex FMP54

Related product manuals