Levelflex FMP51, FMP52, FMP54
114 Endress+Hauser
Customized parametrization
If the option IJ "Customized parametrization HART", IK "Customized parametrization PA" or IL
"Customized parametrization FF" has been selected in feature 570 "Service", customer specific
presettings can be selected for the following parameters:
Parameter Communication Selection list / range of
values
Setup → Distance unit • HART
• PA
• FF
• in
• mm
Setup → Empty calibration • HART
• PA
• FF
0 to 45 m (0 to 147 ft)
Setup → Full calibration • HART
• PA
• FF
0 to 45 m (0 to 147 ft)
Setup → Adv. Setup → Current output 1/2 → Damping HART 0 to 999.9 s
Setup → Adv. Setup → Current output 1/2 → Failure mode HART • Min
• Max
• Last valid value
Setup → Adv. Setup → Current output 1/2 → Burst mode HART • Off
• On