Levelflex FMP51, FMP52, FMP54
Endress+Hauser 31
Power supply
An external power supply is required.
Various supply units can be ordered from Endress+Hauser: see "Accessories" section → 124
2-wire, 4-20mA HART, passive
2-wire; 4-20mA HART
1)
"Approval"
2)
Terminal voltage U at the device Maximum load R, depending on the supply voltage U
0
at the
supply unit
• Non-Ex
• Ex nA
• CSA GP
11.5 to 35 V
3)
R [ ]W
[V]U
0
10
11.5 22.5
20 30 35
0
500
A0014076
Ex ic 11.5 to 32 V
3)
Ex ia / IS 11.5 to 30 V
3)
• Ex d / XP
• Ex ic[ia]
• Ex tD / DIP
13.5 to 30 V
4)
R [ ]W
[V]U
0
10
13.5 24.5
20 30
0
500
A0014077
1) Feature 020 of the product structure: option A
2) Feature 010 of the product structure
3) For ambient temperatures T
a
≤ -30 °C (-22 °F) a minimum voltage of 14 V is required for the sartup of the device at the MIN error current (3,6
mA). The startup current can be parametrized. If the device is operated with a fixed current I ≥ 4,5 mA (HART multidrop mode), a voltage of U ≥
11,5 V is sufficient throughout the entire range of ambient temperatures.
4) For ambient temperatures T
a
≤ -20 °C (-4 °F) a minimum voltage of 16 V is required for the startup of the device at the MIN error current (3.6
mA).
2-wire; 4-20 mA HART, switch output
1)
"Approval"
2)
Terminal voltage U at the device Maximum load R, depending on the supply voltage U
0
at the
supply unit
• Non-Ex
• Ex nA
• Ex nA[ia]
• Ex ic
• Ex ic[ia]
• Ex d[ia] / XP
• Ex ta / DIP
• CSA GP
12 to 35 V
3)
R [ ]W
U
0
[V]
10
12 23
20 30 35
0
500
A0019136
• Ex ia / IS
• Ex ia + Ex d[ia] / IS + XP
12 to 30 V
3)
1) Feature 020 of the product structure: option B
2) Feature 010 of the product structure
3) For ambient temperatures T
a
≤ -30 °C (-22 °F) a minimum voltage of 14 V is required for the startup of the device at the MIN error current (3.6
mA).