EasyManua.ls Logo

Endress+Hauser Levelflex FMP54 - Page 32

Endress+Hauser Levelflex FMP54
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex FMP51, FMP52, FMP54
32 Endress+Hauser
2-wire; 4-20mA HART, 4-20mA
1)
"Approval"
2)
Terminal voltage U at the device Maximum load R, depending on the supply voltage U
0
at the
supply unit
alle Channel 1:
13.5 to 30 V
3)
R [ ]W
[V]U
0
10
13.5 24.5
20 30
0
500
A0014077
Channel 2:
12 to 30 V
R [ ]W
VU
0
[ ]10
12 23
20 30
0
500
A0022583
1) Feature 020 of the product structure: option C
2) Feature 010 of the product structure
3) For ambient temperatures T
a
≤ -30 °C (-22 °F) a minimum voltage of 16 V is required for the startup of the device at the MIN error current (3.6
mA).
Polarity reversal
protection
Yes
Admissible residual ripple
at f = 0 to 100 Hz
U
SS
< 1 V
Admissible residual ripple
at f = 100 to 10000 Hz
U
SS
< 10 mV

Table of Contents

Other manuals for Endress+Hauser Levelflex FMP54

Related product manuals