Levelflex FMP51, FMP52, FMP54 PROFIBUS PA Mounting
Endress+Hauser 21
L
CAUTION
The plugs of the connection cable may be damaged by mechanical stress.
Mount the probe and the electronics housing tightly before connecting the cable.
Lay the cable such that it is not exposed to mechanical stress. Minimum bending radius:
100 mm (4").
When connecting the cable: Connect the straight plug before the angled one. Torque for
both coupling nuts: 6 Nm.
If the meeasuring point is exposed to strong vibrations, an additional locking compound
(e.g. Loctite 243) can be applied at the plug connectors.
Mounting the electronics housing
122 (4.8)
52 (2)
86
(3.4)
70
(2.8)
140 (5.5)
158 (6.2)
175 (6.9)
A B
ø42...60
(1.65...2.36)
A0014793
 4 Mounting the electronics housing using the mounting bracket; dimensions: mm (in)
A Wall mounting
B Pipe mounting
Connecting the cable
Required tools:
Open-end wrench 18AF