EasyManua.ls Logo

Endress+Hauser Levelflex FMP54 - Power Supply

Endress+Hauser Levelflex FMP54
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex FMP51, FMP52, FMP54 PROFIBUS PA Electrical connection
Endress+Hauser 29
7.1.3 Power supply
PROFIBUS PA, FOUNDATION Fieldbus
"Power supply; Output"
1)
"Approval"
2)
Terminal voltage
E: 2-wire; FOUNDATION Fieldbus, switch output
G: 2-wire; PROFIBUS PA, switch output
Non-Ex
Ex nA
Ex nA[ia]
Ex ic
Ex ic[ia]
Ex d[ia] / XP
Ex ta / DIP
CSA GP
9 to 32 V
3)
Ex ia / IS
Ex ia + Ex d[ia] / IS + XP
9 to 30 V
1) Feature 020 of the product structure
2) Feature 010 of the product structure
3) Input voltages up to 35 V will not spoil the device.
Polarity sensitive No
FISCO/FNICO compliant
according to IEC 60079-27
Yes
7.1.4 Overvoltage protection
If the measuring device is used for level measurement in flammable liquids which requires the
use of overvoltage protection according to DIN EN 60079-14, standard for test procedures
60060-1 (10 kA, pulse 8/20 μs), overvoltage protection has to be ensured by an integrated or
external overvoltage protection module.
Integrated overvoltage protection
An integrated overvoltage protection module is available for 2-wire HART as well as
PROFIBUS PA and FOUNDATION Fieldbus devices.
Product structure: Feature 610 "Accessory mounted", option NA "Overvoltage protection".
Technical data
Resistance per channel 2 * 0.5 Ω max
Threshold DC voltage 400 to 700 V
Threshold impulse voltage < 800 V
Capacitance at 1 MHz < 1.5 pF
Nominal arrest impulse voltage (8/20 μs) 10 kA

Other manuals for Endress+Hauser Levelflex FMP54

Related product manuals