Levelflex FMP51, FMP52, FMP54 PROFIBUS PA Integration into a PROFIBUS network
Endress+Hauser 33
GSD file Information and files under:
www.endress.com
www.profibus.org
GSD file version
8.2 Set device address
2
98
3
4
5 6
7
8
1
DIP
ON
A0015686
 7 Address switches in terminal compartment
8.2.1 Hardware adressing
1. Set switch 8 to "OFF".
2. Define the address with switches 1 to 7 according to the table below.
The address change becomes effective after 10 seconds. The device restarts automatically.
Switch 1 2 3 4 5 6 7
Value in position "ON" 1 2 4 8 16 32 64
Value in position "OFF" 0 0 0 0 0 0 0
2
98
3
4
5 6
7
8
1
DIP
ON
2 + 8 = 10
A0015902
 8 Example of hardware addressing: switch 8 is in position "OFF"; switches 1 to 7 define the address.
8.2.2 Software addressing
1. Set switch 8 to "ON".