Integration into a PROFIBUS network Levelflex FMP51, FMP52, FMP54 PROFIBUS PA
32 Endress+Hauser
mm(in)
3(0.12)
A0013661
7.3 Post-connection check
m
Are cables or the device undamaged (visual inspection)?
m
Do the cables comply with the requirements?
m
Do the cables have adequate strain relief?
m
Are all cable glands installed, firmly tightened and correctly sealed?
m
Does the supply voltage match the specifications on the transmitter nameplate?
m
Is the terminal assignment correct →  26?
m
If required: Is the protective earth connected correctly ?
m
If supply voltage is present: Is the device ready for operation and do values appear on the display
module?
m
Are all housing covers installed and firmly tightened?
m
Is the securing clamp tightened correctly?
8 Integration into a PROFIBUS network
8.1 Overview of the device database files (GSD)
Manufacturer ID 17 (0x11)
Ident number 0x1558
Profile version 3.02