Levelflex FMP51, FMP52, FMP54 PROFIBUS PA Commissioning (via operating menu)
Endress+Hauser 41
10.5 Configuration of a level measurement
F
L
D
E
20 mA
100%
4 mA
0%
LN
R
A0011360
 12 Configuration parameters for level measurements in liquids
LN = Length of probe R = Reference point of the measurement
D = Distance E = Empty calibration (= Zero point)
L = Level F = Full calibration (= span)
1. Setup → Device tag
Enter tag for measuring point.
2. Setup → Device address
Enter bus address of the device (only in case of software addressing).
3. Setup → Distance unit
Select distance unit.
4.
Setup → Operating mode
1)
Select Level option.
5. Setup → Tank type
Select tank type.
6. Setup → Tube diameter (only if "Tank type" = "Bypass / pipe")
Enter the diameter of the bypass or stilling well.
1) only visible for devices with "interface measurement" application package